General Functions; Outdoor-Temperature-Dependent Deactivation; Summer Mode - Samson TROVIS 5500 Operating Instructions Manual

Automation system, programmable logic controller plc, standard application for lag/lead sequence wt71
Table of Contents

Advertisement

General functions

7
General functions
7.1

Outdoor-temperature-dependent deactivation

The controllers switches to the stand-by mode when the outdoor temperature exceeds the
Temperature-dependent limit for summer mode parameter. When the outdoor temperature falls
below the limit, heating starts again. This function is activated by default.
2
[Übersicht > Parameter > Allgemein > Sommerbetrieb]
Parameter
ta-GW unm. Sommerbetri
(temperature-dependent limit for

summer mode)

Note: The outdoor-temperature-dependent deactivation works separately from the summer
mode function.
7.2
Summer mode
Summer mode is activated depending on the mean daytime temperature (measured between
7.00h and 22.00h) during the desired period. If the mean daytime temperature exceeds the
Outdoor temperature limit on two successive days within the active time period, summer mode
is activated on the following day.
If the mean daytime temperature remains below the Outdoor temperature limit on one day,
summer mode is deactivated on the following day.
2
[Übersicht > Parameter > Allgemien > Sommerbetrieb]
Parameters
Zeitraum
(time period)
Außentemp. Grenzwert
(outdoor temperature limit)
36
EB 5571-2 EN
WE
Adjustment range
22 °C
0 to 50 °C
WE
Adjustment range
01.06 to 30.09
As required
18 °C
0 to 40 °C