● When 0% Signal Lock is selected:
The pulse output and the analog output are respectively fixed to 0 Hz and mA.
Fixed of the outputs will be cancelled by stopping the input.
● When Auto Zero is selected:
The zeroing of flowrate is performed.
● When Reset Total is selected:
This transmitter has the counter (Counter) and totalizer (Totalizer) that are linked to the pulse
output. The Counter and the Totalizer will be reset to 0.
8.8 Status Output Function
This equipment can assign status input or status output function to the STATUS I/O terminal.
Also, the output of Analog output can be set as status output signal of " / 0 mA" .
Switching between status input and status output can be done by changing the parameter (Status IO
Assign) setting.
Parameter
Analog Assign
Status IO Assign
Output function
Drive out point
Output logic
(NOTE) ※:"Status output" setting can not be set in duplicate for Analog Assign and for Status IO
Assign.
■Status output setting method
()Set function assigning of status output.
Set Analog Assign or Status IO Assign to "Status output" .
()Set assigning of status output.
Select Output function from the following items and assign.
Error status...Output of error status or other status selected by [Err St Select].
Bi Direction...Output of Forward / Reverse flow direction. Refer to ". Bidirectional Flowrate
Output Function".
H/L Alarm...Output of higher / lower limit alarm. Refer to ". Higher / Lower limit alarm function" .
Drive Out Alarm...Drive output alarm
No Function...No function is available.
Descriptions
Assigning of Analog output (※)
Assigning of status input / output
function(※)
Selecting of status output
Drive output alarm setting value
Status output logic
Setting range
Analog / Status output
Status input / Status output
Error Status / Bi Direction
H/L Alarm / Drive Out Alarm
No Function
0 to 00 [%]
Negative / Positive
L-770HP--E
Standard value
Analog
Status input
No Function
00 %
Negative