Table A- 13
ACT_1, ACT_2
ERR_1, ERR_2
PRE_1, PRE_2 *
RxD_1, RxD_2
*) In multitag operation, this LED uses a flashing interval to indicate the number of data carriers
currently within the range of the reader.
Table A- 14
Flashes
Flashes
– = Status not relevant
Other ASM operating modes are indicated by the PRE, ERR, SF, ACT and ON LEDs:
FB 45 for MOBY U, MOBY D, RF200, RF300
Function Manual, 07/2012, J31069-D0166-U001-A4-7618
Status LEDs for ASM 456
LEDs
ON
Lights up when there is logic voltage applied to the CM (is generated from the 24
V supply voltage.)
24 V DC
Lights up when the 24 V supply voltage is connected to the CM.
The corresponding reader is active in processing a user command.
A flashing pattern indicates the last error to occur (see section "Error messages
(Page 47)").
Indicates the presence of a tag.
Indicates live communication with the reader. May also indicate malfunctions on
the reader.
LED display for PROFIBUS diagnostics
BF
SF
On
–
ASM is in start-up mode.
•
Connection to DP Master failed.
•
ASM not detecting a baud rate
•
Bus interrupt
•
DP Master not functioning
•
On
The project data sent to the ASM by
•
the DP Master do not match the
configuration of the ASM.
–
ASM has detected the baud rate, but
•
is not activated by the DP Master.
ASM has not been assigned project
•
plans.
On
Flashe
There is a hardware defect in the
•
s
ASM.
Off
On
Diagnostics available
•
On
Off
The set PROFIBUS address is
•
incorrect or greater than 99.
Meaning
Cause of error
Brief description of the hardware
A.3 ASM 456
Error correction
–
Check the PROFIBUS DP
•
connection.
Check the DP Master
•
Check all cables on your
•
PROFIBUS DP network.
Check whether the connector
•
plugs for the PROFIBUS DP are
securely plugged into the ASM.
Check the project for the ASM
•
(input/output, PROFIBUS
address).
Correct GSD file being used?
•
Check the PROFIBUS address set
•
in ASM and/or in the project
software.
Check the project for the ASM
•
(station type).
Replace the ASM.
•
Evaluate the diagnostic
•
information.
Set the address in the range 1 to
•
99 and carry out new start-up.
93