4.5 ROOM CO TESTING
Select "Room CO" to measure and record CO readings for up to 30 minutes.
SELECT
ROOM CO
TEST TYPE
GENERAL
TEST TYPES
GENERAL:
SWEEP TEST:
MIGRATION TEST:
TYPE C SEALED APPLIANCE:
TYPE B BOILER OPEN FLUE:
TYPE A COOKER:
TYPE A WATER HEATER:
TYPE A SPACE HEATER:
Press
/
Use
the following:
15 minute test with results
stored every minute
2 minute test with max reading
stored at end
15 minute test with results
stored every minute
15 minute test with results
stored every minute
15 minute test with results
stored every minute
30 minute test with results
stored every miute
5 minute test with results
stored every minute
30 minute test with results
stored every 1 minute
to start Room CO testing.
/
to select the test type from
LIMIT = 10ppm
ALARM = 30 ppm
LIMIT = 10ppm
ALARM = 30 ppm
LIMIT = 10ppm
ALARM = 30 ppm
LIMIT = 10ppm
ALARM = 30 ppm
LIMIT = 10ppm
ALARM = 30 ppm
LIMIT = 30ppm
ALARM = 90 ppm
LIMIT = 10ppm
ALARM = 30 ppm
LIMIT = 10ppm
ALARM = 30 ppm