Alarming - Trane Tracer UC600 Integration Manual

For packaged outdoor air unit
Table of Contents

Advertisement

Alarming

The UC600 unit for Packaged Outside Air Units has several objects used for communicating
alarms to the system.
Table 11. Alarm objects
Object Type
BI2
ESTOP
BI3
Filter Status
Supply Fan Failure
BV1
Diagnostic: OAD Proving
BV3
Switch
Diagnostic: Discharge Air
BV6
Temperature Source
Failure
Low Temp Lockout
BV10
Diagnostic: Space
BV11
Temperature Source
Failure
Diagnostic: Space
BV12
Humidity Source Failure
Diagnostic: Outdoor Air
BV13
Temperature Source
Failure
Diagnostic: Outdoor Air
BV14
Humidity Source Failure
High Temp Lockout
BV15
System LOCKOUT
BV17
Diagnostic: ERV Leaving
BV32
Air Conditions Failure
Diagnostic: Heat Failure
BV42
BAS-SVP18D-EN
Object Name
Description
Normal open input.
• 0 = Normal
• 1 = ESTOP
Normal open input.
• 0 = Clean
• 1 = Clogged
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
• Latching diagnostic.
Cleared with Alarm Reset
or power cycle.
• 0 = Normal
• 1 = Fail
Notification Class
2
4
2
2
2
2
2
2
2
2
2
2
2
2
33