Fuel Cell - Viessmann Vitovalor PT2 E11T Installation And Service Instructions Manual

Table of Contents

Advertisement

Heating circuit 1, Heating circuit 2, Heating...
1397.0 "Heating limit: Economy function, outside temperature, heating circuit 3"
Setting
25 °C
1398.0 "Heating limit: Economy function, outside temperature, heating circuit 4"
Setting
25 °C

Fuel cell

Note
Parameter values in bold are factory settings.
600.0 "Reset fuel cell service counter"
Setting
OFF
ON
1097.0 "Export price, electrical energy per kWh"
Setting
1097.2 "Purchase price, electrical energy per kWh"
Setting
(cont.)
Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25
Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35
Temperature limit adjustable from 10 to 35 °C in 1 °C
increments
Explanations
Heating circuit pump logic function (summer economy
control): Heating circuit pump switches off when out-
side temperature 1 K above selected value. Heating
circuit pump switches back on when outside tempera-
ture 1 K below selected value.
25
Delivered condition: Heating limit at outside tempera-
ture 25 °C
10 to 35
Temperature limit adjustable from 10 to 35 °C in 1 °C
increments
Explanations
Reset service counter once service has been carried
out.
0
Service counter reset
1
Reset the service counter.
Explanations
Export price for electrical energy per kWh
0.043
Export price in the delivered condition 0.043
0.001 to
Adjustable from 0.001 to 5.0
5.0
Explanations
Purchase price for electrical energy per kWh
0.258
Purchase price in the delivered condition 0.258
0.001 to
Adjustable from 0.001 to 5.0
5.0
System configuration (parameters)
95