Commissioning/Service - Viessmann Vitovalor PT2 E11T Installation And Service Instructions Manual

Table of Contents

Advertisement

Commissioning/service reports
Commissioning/service reports
Settings and test values
Static pressure
Supply pressure (flow pres-
sure)
For natural gas E
For natural gas LL
Tick gas type.
Carbon dioxide content CO
At lower heating output
At upper heating output
Oxygen content O
*2
2
At lower heating output
At upper heating output
Carbon monoxide content CO
At lower heating output
At upper heating output
Fuel cell module
Electrical output
Power generated
Amount of gas consumed
Hours run
Distilled water cartridge re-
placed
Air filter A replaced
Air filter B replaced
CO sensor replaced
If the fuel cell module is in operation when the measurement is taken, the result may be below the set value.
*1
If the fuel cell module is in operation when the measurement is taken, the result may be above the set value.
*2
200
Set
value
Date
Signa-
ture
mbar
30
kPa
3.0
mbar
17.4-2
kPa
5
1.74-2.
5
*1
2
% by
7.5-9.5
vol.
% by
7.5-9.5
vol.
% by
4.0-7.6
vol.
% by
4.0-7.6
vol.
ppm
< 1000
ppm
< 1000
W
750
kWh
m
3
h
Commis-
Mainte-
sioning
nance/
service
Maintenance/
Maintenance/
service
service