1102.0 "Min. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
1102.1 "Max. speed of speed-controlled primary/heating circuit pump in standard mode, heating circuit 1"
Setting
1192.0 "Minimum flow temperature limit, heating circuit 1"
Setting
20 °C
1192.1 "Maximum flow temperature limit, heating circuit 1"
Setting
74 °C
1193.0 "Minimum flow temperature limit, heating circuit 2"
Setting
20 °C
1193.1 "Maximum flow temperature limit, heating circuit 2"
Setting
74 °C
1194.0 "Minimum flow temperature limit, heating circuit 3"
Setting
20 °C
(cont.)
Explanations
Minimum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Minimum speed adjustable from 0 to 100 %
Explanations
Maximum speed of the internal circulation pump in
heating mode with standard room temperature
...
Delivered condition specified by settings specific to
the heat generator
0 to 100
Maximum speed adjustable from 0 to 100 %
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters
Explanations
Maximum flow temperature limit for the heating circuit
74
Maximum limit in the delivered condition 74 °C
10 to 100
Setting range limited by heat generator-specific pa-
rameters
Explanations
Minimum flow temperature limit for the heating circuit
20
Minimum limit in the delivered condition 20 °C
1 to 90
Setting range limited by heat generator-specific pa-
rameters