Viessmann Vitovalor PT2 E11T Installation And Service Instructions Manual page 120

Table of Contents

Advertisement

Troubleshooting
Fault messages for gas condensing module
Fault number
System characteristics
on the display
F.402
Burner in a fault state
F.403
Burner in a fault state
F.404
Burner in a fault state
F.405
Burner in a fault state
F.406
Burner in a fault state
F.407
Burner in a fault state
F.408
Burner in a fault state
F.409
Burner in a fault state
F.410
Burner in a fault state
F.415
No current electricity meter
values
F.416
Burner locked out
F.417
Burner locked out
F.418
Burner locked out
120
(cont.)
Cause
Lead break, ionisation
voltage, signal 2
Short circuit, dynamic ioni-
sation current, signal 1
Lead break, dynamic ioni-
sation current, signal 1
Short circuit, dynamic ioni-
sation current, signal 2
Lead break, dynamic ioni-
sation current, signal 2
Safety chain
Gas valve, relay 1
Gas valve, relay 2
Internal error, processor
Communication error on
M-bus
Flue gas temperature sen-
sor incorrectly positioned
Short circuit, 24 V power
supply
Lead break, 24 V power
supply
Measures
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check heating system fill level.
Check circulation pump.
Vent the system.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check ignition electrodes and con-
necting cables.
Check ionisation electrode and
connecting cable.
Reset burner.
Check connection to M-bus gate-
way.
Fit flue gas temperature sensor
correctly (see page 130).
Check connecting lead and supply
voltage to the burner control unit.
Check connecting lead and supply
voltage to the burner control unit.