Rockwell Automation Allen-Bradley SynchLink 1756-DM Series Design Manual page 95

Table of Contents

Advertisement

Table 1.6
1751-SLBP SynchLink Bypass Switch Block Specifications
Fiber Optic Cable
Fiber Type
Fiber Termination Type
Assemblies
Maximum Length
Minimum Length
Power Conductors
Wire Size
Category
Maximum Length
Digital Input
ON-State Voltage
ON-State Current
OFF-State Voltage
Isolation Voltage
Conductors
Wire Size
Category
Maximum Length
Agency Certifications
1
This product must be mounted within a suitable system enclosure to prevent personal injury resulting from
accessibility to live parts. The interior of this enclosure must be accessible only by the use of a tool. This
industrial control equipment is intended to operate in a Pollution Degree 2 environment, in overvoltage
category II applications, (as defined in IEC publication 664A) at altitudes up to 2000 meters without
derating.
2
Use this category information for planning conductor routing as described in publication 1770-4.1,
"Industrial Automation Wiring and Grounding Guidelines."
200/230 micron HCS (Hard Clad Silica)
Versalink V-System
Cable assemblies can be ordered from Rockwell
Automation, catalog number 1403-CFxxx
(xxx = length in meters); or from Lucent
Technologies, Specialty Fiber Technologies division.
300m
1m
12 gauge maximum, 24 gauge minimum (#12 AWG
to 24 AWG), stranded
2
2
3m
Isolated, sinking
12V dc minimum
24V dc nominal
30V dc maximum
12mA nominal @ 24V dc
8V dc maximum
850V dc
Use shielded two-conductor cable
12 gauge maximum, 24 gauge minimum (#12 AWG
to 24 AWG), stranded
2
2
10m
Listed Industrial Control Equipment
Certified Process Control Equipment
Certified Class I, Division 2, Groups A, B, C, D
Marked for all applicable directives
Marked for all applicable acts
N223
Publication 1756-TD008A-EN-P - August 2002
A-9