A-2
Publication 1756-TD008A-EN-P - August 2002
Table 1.1
1756-SYNCH SynchLink Module Specifications
Frame Period
Indicators
Environmental Conditions
1
Operating Temperature
Storage Temperature
Relative Humidity
Shock
Operating
Non-Operating
Vibration
Agency Certifications
1
This product must be mounted within a suitable system enclosure to prevent personal injury resulting from
accessibility to live parts. The interior of this enclosure must be accessible only by the use of a tool. This
industrial control equipment is intended to operate in a Pollution Degree 2 environment, in overvoltage
category II applications, (as defined in IEC publication 664A) at altitudes up to 2000 meters without
derating.
5 0m s
Green and red indicators for operation,
status and diagnostics
0ºC - 60ºC (32ºF - 140ºF)
-40ºC - 85ºC (-40ºF - 185ºF)
5 to 95%, 0ºC - 60ºC non-condensing
30g peak acceleration, 11 ( ± 1)ms pulse width
50g peak acceleration, 11 ( ± 1)ms pulse width
Tested 2g @ 10-500Hz per IEC 68-2-6
Listed Industrial Control Equipment
Certified Process Control Equipment
Certified Class I, Division 2, Groups A, B, C, D
Marked for all applicable directives
Marked for all applicable acts
N223