Estimating Cable Lengths

Chapter Summary

Publication 1756-TD008A-EN-P - August 2002
The SynchLink system requires the use of pre-terminated cable
assemblies. SynchLink fiber optic cable segments are limited to a
maximum of 300m. If your distance requirements are greater than
300m, you need to revise your floor plan.
Avoid jointing your cable. Splicing adapters can
IMPORTANT
cause considerable attenuation and limit the
maximum length of your system. Make sure to check
the attenuation of different cable sections after the
cable is installed.
In this chapter, you read about planning a SynchLink fiber optic
cable system.
Chapter 7 explains Installing a SynchLink Fiber Optic Cable System.