Samson TROVIS 5500 Operating Instructions Manual page 75

Automation system, programmable logic controller plc, standard application for lag/lead sequence wt71
Table of Contents

Advertisement

Parameters
Klappenlaufzeit
(shut-off valve transit
time)
Control parameters
Kp
Tn
Tv
Ty
Adjustment
WE
range
0 to 300 min
3 min
0.1 to 99.9
1.0
0 to 999 s
30 s
0 to 999 s
0 s
15 to 600 s
45 s
Comments
Time waited until circulation pump activated
Gain factor of heat exchanger control circuit
Reset time of heat exchanger control circuit
Derivative-action time of heat exchanger control cir-
cuit
Valve transit time of heat exchanger control circuit
Appendix
75
EB 5571-2 EN