Functions of the heat exchanger

4.3.2 Capacity-dependent change

The lead heat exchanger is the heat exchanger which had the lowest average output capacity
over the past three days.
2
[Übersicht > Parameter > Allgemein > Folgebetrieb]
Parameter
Führungswechsel (sequence
change) = Leistung (rating)

4.3.3 Operating hours-dependent change

The Time interval for lag/lead sequence change parameter determines after how many opera-
ting hours a sequence change can take place.
Parameter
Führungswechsel (sequence
change) = Betreib-Std (operating
hours)
Folgeumkehr-Intervall
(time interval for lag/lead se-
quence change)
4.4

Smooth start-up

The smooth start-up function prevents the lead heat exchanger from overheating in problematic
systems by reducing the lead heat exchanger to 50 % (control output) before activating the lag
heat exchanger.
Parameter
Sanftanlauf (smooth start-up) =
EIN (on)
Folgeumkehr-Intervall
(time interval for lag/lead se-
quence change)
26
EB 5571-2 EN
WE
Adjustment range
AUS
Outdoor temp., rating, operating hours, OFF
WE
Adjustment range
AUS
Outdoor temp., rating, operating hours, OFF
168 h
1 to 999 h
WE
Adjustment range
AUS
EIN (on), AUS (off)
168 h
1 to 999 h