Functions Of The Heat Exchanger; Parallel Operation; Lag/Lead Sequence Control - Samson TROVIS 5500 Operating Instructions Manual

Automation system, programmable logic controller plc, standard application for lag/lead sequence wt71
Table of Contents

Advertisement

Functions of the heat exchanger

2
[Übersicht > Parameter > Allgemein]
Parameters
Pumpennachlaufzeit
(pump lag time)
Vorlaufgrenzwert
(supply flow limit)
4
Functions of the heat exchanger
4.1

Parallel operation

This function leads to all boilers working constantly in parallel (no lag/lead sequence control).
The boilers start operating one after the other, taking into account the programmed time sched-
ules: Min. deactivation time and Sequence delay as well as taking into account Temperature to
enable lag/lead sequence.
2
[Übersicht > Parameter > Allgemein > Folgebetrieb]
Parameters
Folge (sequence) = parallel
Folgefreigabetemp.
(temperature to enable lag/lead
sequence)
Folgeverzögerung
(sequenc delay)
2
[Übersicht > Parameter > Wärmetauscher 1...3]
Parameters
Ausschaltzeit min
(min. deactivation time)
4.2

Lag/lead sequence control

The heat exchangers are enabled depending on the configuration:
4
Enabled = EIN (on)
The heat exchanger is only enabled by the heat exchanger enabling function (see section
1.5.1).
22
EB 5571-2 EN
WE
Adjustment range
5 min
0 to 90 min
55 °C
20 to 120 °C
WE
Adjustment range
Depending on
Outdoor temperature dependent, unrestricted,
outdoor temp.
parallel
12 °C
–40 to 50 °C
10 min
0 to 90 min
WE
Adjustment range
0 min
0 to 90 min