Samson TROVIS 5500 Operating Instructions Manual page 83

Automation system, programmable logic controller plc, standard application for lag/lead sequence wt71
Table of Contents

Advertisement

Parameters
Montag - Sonntag
(Mon - Sun)
Montag (Mon)
Dienstag (Tues)
Mittwoch (Wed)
Donnerstag (Thurs)
Freitag (Fri)
Samstag (Sat)
Sonntag (Sun)
Feiertage (public holidays)
St.-Nr. (ext. Bedarf)
St. no. (external demand)
Begrenzung Xw Auf (°C)
(limit Xw OPEN)
Separater Sollwert
(separate set point)
Sollwert Anf.
(set point demand)
Vorlaufgrenzwert
(flow limit)
Außentemperatur senden
St.-Nr.
1)
(send outdoor temp.)
Rücklaufbegrenzung
1)
(return flow limit)
Externer Bedarf (0V)
1)
(external demand)
Externer Bedarf (10V)
1)
(external demand)
1)
Firmware version 1.50 and higher
Adjustment range
As required
As required
AUS, 5 to 999
AUS, 2 to 10 °C
EIN (on), AUS (off)
20 to 120 °C
20 to 120 °C
AUS, 5 to 255
0.1 to 2.0
0 to 150 °C
0 to 150 °C
WE
Comments
Block entry for all days of the week
Separate entry for each day of the week
7.00 to
22.00 h
NOTE!
The block entry writes over all
times-of-use programmed separately for a
day of week.
Address of station, from which the ex-
ternal set point for transfer over Modbus
AUS
is given
Attenuation intensity for the condensate
AUS
accumulation control
AUS
Activation/input of the fixed set point
Sollwert Anf.
65 °C
Flow temperature limit under which pump
55 °C
lag time is ended.
AUS
0.1
Range for external demand during
0 °C
transfer over an analog signal to UE2
120 °C
Appendix
83
EB 5571-2 EN