9.1.4 General

2
[Übersicht > Parameter > Allgemein]
Parameters
Vorlauftemp.-Sollwert
(flow temp. set point)
Absenkdifferenz
(set-back difference)
Vorlauftemp. max
(max. flow temp.)
Vorlauftemp. min
(min. flow temp.)
Rücklauftemp. max
(max. return flow temp.)
Rücklauftemp. min
(min. return flow temp.)
Pumpennachlaufzeit
(pump lag time)
Folgebetrieb (sequence operation)
Adjustment range
20 to 160 °C
0 to 30 °C
20 to 120 °C
20 to 120 °C
20 to 120 °C
20 to 120 °C
0 to 90 min
WE
Comments
70 °C
Set point for fixed set point control
Set-back of flow temperature set point
during unoccupied time (fixed set point
15 °C
control)
90 °C
Flow temperature limitation of entire sys-
tem
20 °C
65 °C
Return flow temperature limitation of enti-
re system
20 °C
Time waited until shut-off valves close
5 min
Appendix
81
EB 5571-2 EN