Samson TROVIS 5500 Operating Instructions Manual page 82

Automation system, programmable logic controller plc, standard application for lag/lead sequence wt71
Table of Contents

Advertisement

Appendix
Parameters
Folge (sequence)
EIN-Schaltpunkt
(ON switching point)
AUS-Schaltpunkt
(OFF switching point)
Folgefreigabetemp.
(temperature for en-
abling the sequence)
Folgeverzögerung
(sequence delay)
Führungswechsel
(sequence change)
Folgeumkehr-GW ta
(reverse sequence li-
mit ta)
Folgeumkehr-Intervall
(time interval for
lag/lead sequence
change)
Sanftanlauf
(smooth start-up)
Sommerbetrieb
tA-GW unm.
Sommerbetri
(temperature-de-
pendent limit for
summer mode)
Zeitraum
(time period)
Außentemp. Grenz-
wert
(outdoor temperature
limit)
Nutzungszeiten
(times-of-use)
82
EB 5571-2 EN
Adjustment range
Outdoor temperature
dependent, unrestric-
ted, parallel
0 to 100 %
0 to 100 %
–40 to 50 °C
0 to 90 min
Outdoor temp., rating,
operating hours, OFF
–40 to 50 °C
1 to 999 h
EIN (on), AUS (off)
0 to 50 °C
As required
0 to 40 °C
WE
Comments
Outdoor
temperature
Condition for sequence operation
dependent
90 %
Unrestricted sequence:
Limits of heat exchanger output
40 %
Outdoor-temperature-dependent se-
12 °C
quence: Outdoor temperature limit
10 min
Time waited until sequence is enabled
AUS
Condition for lead/lag change
Outdoor-temperature-dependent lead/lag
15 °C
change: Outdoor temperature limit
Operating hours-dependent lead/lag
change: Operating hours limit
168 h
Prevent the lead heat exchanger from
AUS
overheating
Limit for outdoor-temperature-dependent
deactivation
22 °C
01.06 to
Application period for summer mode
30.09
Outdoor temperature limit (daily mean):
Summer mode started when the tempera-
18 °C
ture exceeds the limit