9.1.2 Heating circuits HK1, HK2 and HK3

2
[Übersicht > Service > Heizkreis HK1 ... HK3]
This menu can only be selected after the application key number has been entered!
Parameters
Kennlinienart
(type of characteristic)
Regelkreis
(control circuit)
2
[Übersicht > Parameter > Heizkreis HK1 ... HK3]
Parameters
Kennlinie (characteristic)
Außentemp. Punkt1
(outdoor point 1)
Vorlauftemp. Punkt1
(flow point 1)
Außentemp. Punkt2
(outdoor point 2)
Vorlauftemp. Punkt2
(flow point 2)
Absenkdiff. Punkt2
(set-back diff. pt 2)
Außentemp. Punkt3
(outdoor point 3)
Vorlauftemp. Punkt3
(flow point 3)
Absenkdiff. Punkt3
(set-back diff. pt 3)
76
EB 5571-2 EN
Adjustment
WE
range
Four-point,
gradient, fixed
Steigung Condition for controlling the flow temperature
set point
Continuous,
3-Punkt Control algorithm of heating circuit
three-step
Adjustment
WE
range
–20 to 50 °C –10 °C
20 to 160 °C
90 °C
–20 to 50 °C
–5 °C
20 to 160 °C
80 °C
0 to 30
15 °C
°C
–20 to 50 °C
5 °C
20 to 160 °C
68 °C
0 to 30 °C
20 °C
Comments
Comments
Definition of four-point characteristic
(only with type of charateristic = four-point)