9.1.3 DHW heating

2
[Übersicht > Parameter > Warmwasserbereitung]
Parameters
Vorlauftemp.-Sollwert
(flow temp. set point)
Speicher min
(min. storage tank)
Speicher max
(max. storage tank)
Desinfektionstemp.
(disinfection temp.)
NZ therm. Desinfektion
(times-of-use for
thermal disinfection)
Montag - Sonntag
(Mon - Sun)
Montag (Mon)
Dienstag (Tue)
Mittwoch (Wed)
Donnerstag (Thurs)
Freitag (Fri)
Samstag (Sat)
Sonntag (Sun)
Vorrangschaltung
(priority operation)
Nutzungszeiten (times-of-use)
Montag - Sonntag
(Mon - Sun)
Montag (Mon)
Dienstag (Tue)
Mittwoch (Wed)
Adjustment
WE
range
20 to 120 °C
65 °C
20 to 90 °C
40 °C Activation value for storage tank charging
20 to 90 °C
45 °C Dectivation value for storage tank charging
50 to 80 °C
70 °C
Note: Only with active storage tank sensors!
7.00 to
As required
22.00 h
EIN (on),
AUS
AUS (off)
7.00 to
As required
22.00 h
Comments
Flow temperature set point for DHW demand
Storage tank temperature set point for thermal
disinfectio
Block entry for all days of the week
Separate entry for each day of the week
NOTE!
The block entry writes over all times-of-use pro-
grammed separately for a day of week.
Priority of DHW heating
Block entry for all days of the week
Separate entry for each day of the week
NOTE!
The block entry writes over all times-of-use pro-
grammed separately for a day of week.
Appendix
79
EB 5571-2 EN