Four-Point Characteristic - Samson TROVIS 5500 Operating Instructions Manual

Automation system, programmable logic controller plc, standard application for lag/lead sequence wt71
Table of Contents

Advertisement

Functions of the heating circuit

5.1.2 Four-point characteristic

The four-point characteristic allows you to define your own heating characteristic.
The four-point characteristic is defined by four points for Outdoor temperature and for Flow
temperature. The set-back difference is entered for points 1 and 2 as well as points 3 and 4. This
results in the dashed line in Fig. 2.
The Max. flow temperature and Min. flow temperature parameters mark the upper and lower li-
mits of the flow temperature.
t
[˚C]
VL
100
t
VLmax
90
80
70
60
50
40
P4
30
t
20
VLmin
10
20
15
Fig. 2 · Four-point characteristic
2
[Übersicht > Service > Heizkreis 1...3]
This menu can only be selected after the application key number has been entered!
Parameter
Kennlinienart (type of character-
istic) = 4-Punkte (four-point)
2
[Übersicht > Parameter > Heizkreis 1...3 > Kennlinie]
Parameters
Außentemp. Punkt1
(outdoor temp. for point 1)
Vorlauftemp. Punkt1
(flow temp. for point 1)
30
EB 5571-2 EN
P2
P3
10
5
0
–5
WE
Steigung
WE
–10 °C
90 °C
P1 to 4 Points 1 to 4
t
VL
t
P1
A
...min
...max
t
A
[˚C]
–10
–15 –20
Adjustment range
Four-point, gradient, fixed set point
Adjustment range
–20 to
50 °C
20 to 160 °C
Flow temperature
Outdoor temperature
Min. t
VL
Max. t
VL
Four-point characteristic
Reduced four-point characteristic