Start-up
Setting the heat exchanger rating
It is particularly important to set the rating of a heat exchanger if the lag/lead sequence is to de-
pend on the heat exchanger's output capacity. Refer to section 4.2. The rating of all heat ex-
changer is set to 70 kW by default. If the rating of one or more heat exchangers is to be chan-
ged, proceed as follows:
Service
Language
Anlage konfigurieren
Wärmetauscher 1
Wärmetauscher 2
Wärmetauscher 3
Heizkreis 1
Zurück
Wärmetauscher 1
Nennleistung
Regelkreis
Freigabe
Zurück
After configuring the system, exit the menu step-by-step and return to the start screen:
Select 'Zurück' (Back).
Exit overview menu.
Display: Start screen
20
EB 5571-2 EN
Select DHW heating.
Confirm with [Übernehmen].
If the configuration is to rejected:
Select [Verwerfen] on display.
Reject configuration.
The display returns to the service menu.
Select required heat exchanger (Wärmetauscher
1-3).
Activate the editing mode for 'Wärmetauscher x'
Display: Wärmetauscher x (Heat exchanger x)
70kW
3-Punkt
The menu item 'Nennleistung' (Rating) is highlighted.
EIN
Activate the editing mode for rating.
Set the required rating.
Confirm setting.