Resolving A Hardware Problem - IBM Power Systems 8001-12C Manual

Problem analysis, system parts, and locations
Hide thumbs Also See for Power Systems 8001-12C:
Table of Contents

Advertisement

2. Record the names of any sensors that have a red LED indicator status.
Note: Repeat steps 3 - 6 for every sensor that you record in this step.
3. Use one of the following commands to list the sensor event logs (SELs).
v To list SELs by using an in-band network, enter the following command:
ipmitool sel elist
v To list SELs remotely over the LAN, enter the following command:
ipmitool -I lanplus -U <username> -P <password> -H <BMC IP addres or BMC hostname> sel elist
4. Review the list of SELs and locate the log entry that meets the following criteria:
v The name of any of the sensors you recorded in step 2.
v A service action keyword is present. For a list of service action keywords, see "Identifying service
action keywords in system event logs" on page 26.
v Asserted is in the description.
Did you identify a log entry that meets the above criteria?
v Yes: Continue with the next step.
v No: Go to "Collecting diagnostic data" on page 71. Then, go to "Contacting IBM service and
support" on page 71. This ends the procedure.
5. Use one of the following options to display the SEL details for the sensor:
Note: You must specify the SEL record ID in hexadecimal format. For example: 0x1a.
v To display SEL details by using an in-band network, enter the following command:
ipmitool sel get <SEL record ID>
v To display SEL details remotely over the LAN, enter the following command:
ipmitool -I lanplus -U <username> -P <password> -H <BMC IP address or BMC hostname> sel get <SEL record ID>
6. The sensor ID field contains sensor information in the sensor name (sensor ID) format. Record the
sensor name, sensor ID, and event description. Then, use this information to determine the service
action to perform:
v If your system is an 8001-12C or 8005-12N, go to "Identifying a service action by using sensor and
event information for the 8001-12C and 8005-12N" on page 27 to determine the service action to
perform. This ends the procedure.
v If your system is an 8001-22C or 8005-22N, go to "Identifying a service action by using sensor and
event information for the 8001-22C and 8005-22N" on page 43 to determine the service action to
perform. This ends the procedure.

Resolving a hardware problem

Learn how to identify the service action that is needed to resolve a hardware problem.
1. If you have not already done so, manually boot the system.
2. Go to "Identifying a service action by using system event logs" on page 21. Then, continue with the
next step.
3. Was a service action identified?
If
Then
Continue with the next step.
Yes:
No:
Go to step 5 on page 11.
4. Did the service action fix the problem?
If
Then
Yes:
This ends the procedure.
10
Problem analysis, system parts, and locations for the 8001-12C, 8001-22C, 8005-12N, and 8005-22N