Bind signal cables and power cables separately.
Step 3 Route signal cables. Bind cables to the cabinet.
from the top of the cabinet.
Figure 3-38 Routing control cable from the top of the cabinet
----End

3.2.7.2 Bottom Cable Routing

Prerequisites
Issue 07 (2020-01-10)
The number and colors of control cables in
If you choose to route cables from the bottom of the cabinet, ensure sufficient space at the
bottom of the cabinet.
If you choose to route cables through holes, remove power cable tray covers and drill
holes. After you drill holes, paste grommet strip to the hole edge to protect cables.
Reinstall the covers on the cabinet.
After routing cables, use firestop putty to fill in the gap between the cables and the cabinet.
Copyright © Huawei Technologies Co., Ltd.
Figure 3-38
shows the signal cables routed
Figure 3-38
are for reference only.