UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
Total Runtime
Figure 4-15 Total Runtime screen
Issue 07 (2020-01-10)
Current of the battery string. The current is + when batteries are being charged and -
when discharged.
Temperature (° C)
Battery operating temperature (A battery sensor is required. If this sensor is not installed,
NA is displayed.)
Backup time (min)
Battery backup time estimated at the current load.
Remaining cap. (%)
Remaining battery capacity.
Bypass runtime (h)
Time for which the UPS runs in bypass mode.
Inv. runtime (h)
Time for which the UPS runs in inverter mode.
The value takes an integer. For example:
If the value is less than 1, the value takes 0.
If the value is greater than 1 and less than 2, the value takes 1.