UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
To prevent electric shocks, do not touch the copper bar behind the insulation board when
replacing a fuse.
To ensure that the system runs safely, if a fuse is to be replaced, the new fuse must be of the
same type and specifications.
Procedure
Step 1 Remove the rear cover from the bypass cabinet.
Figure 3-34 Removing the rear cover from the bypass cabinet
Step 2 Remove the damaged fuse. Replace the fuse.
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
3 Installation
71