UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
Figure 5-47 Associated intelligent power supply parameters on the LCD 6
Table 5-2 Associated intelligent power supply parameters
Parameter
Working mode
D.G. mode
Intra-rack power module
start delay (s)
Input adaptability
Output freq. track rate
(Hz/s)
D.G. connection [GEN]
MUS05A DO_4
ATS
D.G. startup batt. volt.
(V/cell)
D.G. power limiting (kVA)
D.G. charger power ratio
(%)
Issue 07 (2020-01-10)
In battery mode (non-battery test), if the battery voltage reaches the value specified by D.G. startup
batt. volt. or Low battery voltage, the signal for starting the D.G. is triggered.
Copyright © Huawei Technologies Co., Ltd.
Automatic Settings
ECO
Enable
5
Strong
0.6
Enable
D.G. control
Connected
1.80
N/A
N/A
5 Operations
Remarks
N/A
You cannot modify this
parameter if it is set
automatically.
N/A
N/A
N/A
N/A
N/A
N/A
N/A
Set this parameter to the actual
power of the D.G.
Set this parameter to the
percentage of the power
provided by the charger for
batteries.
182