UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
Figure 5-14 AC Output screen
Figure 5-15 Real-time Data page
If the measured voltages are not within the normal ranges, choose Maint. > Calib. on the
WebUI and expand Power unit. Enter the measured voltages in Ph. A output volt., Ph. B
output volt., and Ph. C output volt. under Actual Value, and click Submit to commission
the voltages.
Issue 07 (2020-01-10)
Check on the WebUI.
On the home page, choose Monitoring > Real-time Data. In the Output area, check the
UPS three-phase output voltage and frequency.