3.2.8 Connecting Ground Cables

Figure 3-42 Layout of the power cable wiring terminals in a PDU
If you do not ground the UPS as required, electromagnetic interference, electric shocks, or fire
disasters may occur.
Issue 07 (2020-01-10)
(1) Mains input
wiring terminal
Before cable connections, ensure that all UPS input switches are OFF. Paste warning
labels to prevent operation on the switches.
Connect input power cables to the UPS and then to customer equipment.
This figure is for reference only. For details about recommended cable specifications and
numbers, see
Table
3-3. Select and install cables based on site requirements.
In the case of top cable routing, the ground cable is routed from the top.
how to route a ground cable from the bottom.
Copyright © Huawei Technologies Co., Ltd.
(2) Battery input
wiring terminal
(3) Output wiring
(4) Bypass input
terminal
wiring terminal
3 Installation
Figure 3-43
shows
79

Advertisement

Table of Contents
loading

This manual is also suitable for: