UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
Figure 5-40 Intelli. Power screen
Step 3 Set Intelligent power to Enabled. In the warning dialog box, tap Yes.
Figure 5-41 Intelligent power parameters on the LCD
When the D.G. is connected, ensure that the preceding three parameters have been set so that the UPS
can run properly.
Issue 07 (2020-01-10)
Intelligent Power
The value can be Enabled or Disabled. The intelligent power supply function can be
used only when Intelligent power is set to Enable. The default value is Disabled.
ATS
The value can be Connected or Not connected. When the value is Connected, the UPS
works in the ATS scenario; when the value is Not connected, the UPS works in the reuse
scenario. The default value is Connected. This parameter is available only after you set
Intelligent Power to Enabled.
D.G. startup batt. volt. (V/cell)
The value ranges from 1.80 to 2.00. The default value is 1.80. This parameter is available
only after you set Intelligent Power to Enabled.