UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
Figure 5-37 Confirmation message
Figure 5-38 Security warning
Step 4 Check that the load power is stable (that is, no transient surge results in overload, which may
cause the UPS to transfer to bypass mode), and tap Yes. A message is displayed, indicating
that the hibernation function is set successfully.
Step 5 Set Module cycle hiber. period (d) to an integer ranging from 1 to 100. The default value is
30.
----End
5.2.2 WebUI
Procedure
Step 1 On the login page, enter a user name and password, and click Login.
Step 2 Choose Monitoring > Param. Settings > Advanced Param..
Issue 07 (2020-01-10)
Copyright © Huawei Technologies Co., Ltd.
5 Operations
177