UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
If the power module receives a startup command when it cannot be started, the startup command will be
kept for 1 minute. If the startup command is not cleared within 1 minute (for example, other faults occur
on the module, or you perform shutdown or rectify faults) and the module can be started, the module
responds to the startup command.
Step 6 After the inverter is started, the UPS transfers to the inverter power supply mode. You can
check the system running status diagram to confirm that the active inverter supplies power to
the system. During test by engineers, check whether the UPS three-phase output voltage and
frequency are normal by monitoring AC Output on the screen, and use a multimeter to check
whether the valid value of three-phase output voltage and frequency are normal.
The three-phase output voltage should be 220 V, 230 V, or 240 V, and the frequency should be 50 Hz or
60 Hz.
Figure 5-13 Common Functions
Issue 07 (2020-01-10)
If you enter incorrect passwords for three consecutive times, you will be locked out for 5 minutes.
e.
On the homepage, choose Monitoring > Control, and click Inv. ON. In the
displayed dialog box, click OK to start the inverter.
Figure 5-12 Starting the inverter
Check on the LCD