UPS5000-E-(360 kVA-480 kVA)
User Manual (40 kVA Power Modules)
Alarm ID
Alarm Name Severity
(Alarm ID-
Cause ID)
0566-1
Output
overload
0570-4
BPM module
abnormal
0583-1
Inter-rack par.
cable
abnormal
0583-4
0583-5
0583-6
0584-2
Inter-rack par.
cable alarm
0584-4
Issue 07 (2020-01-10)
Cause
Minor
The load is
excessive.
Derating reduces
the rated system
power.
The module is
damaged.
Critical
The bypass fan is
not functioning
properly, or the air
channel is blocked.
The ambient
temperature
exceeds the upper
threshold.
The load is
excessive.
Critical
The inter-rack
parallel system
CAN bus is
disconnected or
short-circuited.
Only one rack
works in a parallel
system.
An ECM is faulty.
The inter-rack
industrial frequency
synchronization cable
is broken.
The inter-rack carrier
synchronization cable
is broken.
The intra-rack
INVBYP cable is
broken.
The parallel CAN
bus is broken.
Minor
The inter-rack parallel
cable is faulty.
The inter-rack
industrial frequency
synchronization cable
Copyright © Huawei Technologies Co., Ltd.
Solution
1. Check that there is no overload.
2. Check that the module power is
not derated due to a fan fault.
3. If the alarm persists, replace the
power module.
1. Check the bypass fan and air
channel. If the fan is faulty,
replace it.
2. Check that the ambient
temperature has not exceeded
40° C.
3. Check that there is no overload.
1. Check the inter-rack parallel
system CAN bus.
2. Rectify the disconnection or
short-circuit fault.
3. Replace the ECM.
Replace the inter-rack parallel cable.
Replace the inter-rack parallel cable.
B Alarm List