Dm-2304: 4-Port Din Rail (Db9) Installation - Comtrol DeviceMaster DM-2000 Series Installation And Configuration Manual

Table of Contents

Advertisement

Hardware Installation

DM-2304: 4-Port DIN Rail (DB9) Installation

Use the following procedure to install DM-2304.
1. Attach the DeviceMaster to the DIN rail adapter.
2. Connect the power supply and apply power to the DeviceMaster using the power supply specifications on
the product label and the following information.
Observe proper ESD techniques when connecting and disconnecting the DeviceMaster.
Caution
a. If the DIN rail is not connected to earth ground,
insert the earth ground wire into the chassis
ground screw terminal.
Note: The chassis ground connection is made only if
the DIN rail is NOT connected to earth ground.
b. Insert the DC positive wire into one of the + screw
terminals and the DC return wire into the - screw
terminal.
• A second redundant power supply can be
connected to the unit by inserting the DC
positive wire into the other + screw terminal and
the DC return wire into the - screw terminal.
• The DeviceMaster continues to operate if one of
the two connected power supplies should fail.
Refer to
DM-2304: 4-Port DIN Rail Models Power
Supply
on Page 144 for detailed power
requirements.
c.
Use a small flat head screw driver to lock the wires into place.
d. Verify that each wire has been tightened securely.
e. Connect a UL Listed power supply and UL Listed power cord to a power source to apply power.
Note: Do not connect multiple units until you have changed the default IP address, see
on Page 33.
3. Connect one of the 10/100 ports to the same Ethernet network segment as the host PC using a standard
Ethernet cable. You can daisy-chain another DeviceMaster or Ethernet device to the other port using a
standard Ethernet cable.
4. Verify that the Status LED has completed the boot cycle and network connection for the DeviceMaster is
functioning properly using the following table.
The STATUS LED on the device is lit, indicating you have power and it has completed the
boot cycle.
STATUS
Note: The Status LED flashes while booting and it takes approximately 15 seconds for the
Bootloader to complete the cycle. When the Bootloader completes the cycle, the LED
has a solid, steady light that blinks approximately every 10 seconds.
If the LINK (green) LED is lit, it indicates a working Ethernet connection.
LINK
ACT
If the ACT (yellow) LED flashes, it indicates network activity.
Note: For additional LED information, go to the
22 - Hardware Installation
DM-2304 LED Descriptions
Status LED table
DeviceMaster Installation and Configuration Guide: 2000594 Rev. F
Positive†
Return†
5-30VDC
5-30VDC
PW1
PW2
† Wire gauge: AWG 12-22
on Page 148.
Positive†
Chassis
Ground†
Initial Configuration