Error Messages - INTEGRA Metering CALEC energy master Installation And Operating Instructions Manual

Hide thumbs Also See for CALEC energy master:
Table of Contents

Advertisement

The calibration log records 10 entries with a time stamp, which are relevant for maintaining metro-
logical CE-conformity.
Title/Number
Calibration event
Calibration log 1
Device calibrated
Calibration log 2
Calibration invalid
Calibration log 2
Reset meter readings
Calibration log 4
Calibration log 5
2: E1 Counter overflow
Calibration log 6
3: E1 Counter overflow
Calibration log 7
Calibration log 8
2: E2 Counter overflow
Calibration log 9
3: E2 Counter overflow
18.4

Error messages

Note:
X:... represents calculator No. X ( X = 2 or 3 )
X is only displayed if calculators 2 and 3 are activated.
Message
E1,E2 Counter overflow
X: E1,E2 Counter overflow
Calibration invalid
Th Error CPU module
Tc Error CPU module
Th >< Range error
Tc >< Range error
Th >< Range calc X
Tc >< Range calc X
dT < dTmin-value calc X
Configuration error
Config. error: calc X
Memory error EEPROM
Error real-time clock
Error Display module
No module present
44
E1 Counter overflow
E2 Counter overflow
Description/possible cause
Overflow of the counter on display
Message if calibration seal was destroyed
Measured value outside the measuring
range, temperature sensor miss-
ing/defective, or setting of 2- / 3- / 4-wire
connection incorrect
Temperature on hot/cold side outside the
permitted range
Temperature on hot/cold side is outside
the permitted range for calculator X
Temperature difference is smaller than
dTmin-value
Device configuration in the
Basic settings submenu is incorrect or
incomplete.
Error when saving a parameter or a meter
reading
The real-time clock cannot be accessed
Display module gives error message
No module was found between CPU
Time stamp
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
DD.MM.YY hh:mm
®
CALEC
energy master installation and operating instructions
Note
Date of last 'calibration'
By activating programming mode, the
calibration was invalidated
Resetting the meter readings deletes
the consumption values!
After a counter overflow, the meter
reading is lower than previously. This
can be corrected when calculating con-
sumption, and will still result in correct
consumption values
Comment/action to take
Taken into account during billing
Only possible in programming
mode
Connect sensor correctly
Replace sensor
Check setting of 2-, 3-, 4-wire
connection
Device fault or sensor defect
Device fault or sensor defect
Tc > Th:
When installation idle: error will
disappear when running
Temperature sensors switched:
exchange temperature sensors.
Correct the configuration
Risk of data loss
Device faulty, repair
Device fault, repair
Billing data and logger values no
longer being saved
Replace or repair display module
Device incomplete