Parameters for temperature sensors
The following parameters are available in the Basic settings/Pt100-Input operating menu:
The type of connection can be set in service mode
Pt100-Input 1
Mod-No. 1
Trm.No. 5-1-2-6
Conn.
4-wire
Side T
Hot side
T inst
21.5 °C
T min
-50.0 °C
T max
550.0 °C
T err
999.9 °C
Lot No.
807
HW_No. 12345678
FWV
V01.00.05
Pt100 input 2 has identical parameters with the exception of: Side T Cold side.
Calculator parameters
With the calculator function Energy calculator, the following parameters can be set in service mode
in the submenu Basic settings / application / Fct. :
Application 1
Fct. Energy calc.
<text1
>
<text2
>
T min
0.0 °C
T max
200,0 °C
Parameters for outputs and interfaces
The settings for the output signals and the communication interfaces should be made according to
the device fittings and the system connections.
40
Settable?
Parameter
Select input with the
No
Module number, here the CPU module on the right
No
Terminal numbers
Yes
Type of connection Pt100 (2-, 3-, 4-wire)
No
Temperature sensor installation hot side
No
Instantaneous temperature at input
No
Lowest measurable temperature
No
Highest measurable temperature
Yes
Displayed temperature if an error occurs in the input
No
Production batch number of the module
No
Hardware version module number
No
Firmware version module number
Settable?
Parameter
Select calculator with the
Yes
Function/applications Energy calculator
Text to describe device/measuring point
Lower limit of temperature measureing range
Upper limit of temperature measureing range
®
CALEC
.
keys
energy master installation and operating instructions