Alarm messages, causes and measure

Message
No message
Max. ALARM
Min. ALARM
Flow rate >final value
Pulse/frequency>final value
Measuring tube empty
Input noise
Excitation error
Current output interrupted
Fault Supply voltage

Error messages

Code
Cause
0001
Watch-dog monitor gives error message
0002
Incorrect configuration of the operating data
in EEPROM
0004
Incorrect configuration of the safety data
in EEPROM
0008
EEPROM defective
0010
Programming keys defective or several keys
were pressed simultaneously
0020
Supply voltage (+3.3) outside of tolerance
range
0040
Supply voltage (+13) too low (<10V)
0080
Supply voltage (+13) too high (>14V)
0200
Timeout for input calibration exceeded,
input switch defective.
0400
Input signal overloaded
0800
Interruption of the solenoid coil circuit
flow sensor and transducer.
0C00
Collective alarm 0800 + 0400
32
Fault
Device functions properly
The instantaneous flow rate is greater
than the set maximum limit value
The instantaneous flow rate is less
than the set minimum limit value
The instantaneous flow rate exceeds
the set full scale value
The instantaneous flow rate exceeds the
set full scale value for the pulse or
frequency output
The flow sensor is partially filled, or the empty Verify the process conditions. If necessa-
tube detection is not correctly calibrated.
The measuring signal is affected by external
interfering signals or damaged cable connec- flow sensor. Remove any possible sour-
tion between flow sensor and transducer.
The connections to the solenoid coil are
interrupted or solenoid coil interruption.
The permitted load for the 0/4...20mA current Check the connected load, it must not
output is exceeded.
to 0.
The supply voltage is outside of the
specification.
Measure
Get in contact with our service
Get in contact with our service
Get in contact with our service
Get in contact with our service
Get in contact with our service
Get in contact with our service
Get in contact with our service
Get in contact with our service
Get in contact with our service
Check the cable connections and the correct earthing of the
transducer. Check whether there are any major sources of
interference.
Check the cable connections and the resistance values between
See description of individual codes
Measures
---
Verify the process conditions. Remedy
any possible cause or adjust limit value.
Verify the process conditions. Remedy
any possible cause or adjust limit value.
Verify the process conditions. Remedy
any possible cause or adjust full scale
value.
Change the corresponding parameter,
taking account of the connected device.
ry, calibrate the empty tube detection.
Verify the cabling and earthing of the
ces of interference.
Verify the terminal wire to the sensor.
dexceed 1000 Ohm. To switch off the
alarm, set the ' current fault' parameter
Compare the values with the type plate
specifications.