Chapter 7 Usage of Various Functions

7.1.5 PID control function(Standard type only)

1) Introduction
This chapter will provide information about the built-in PID (Proportional Integral Derivative) function of MASTER-K120S
main unit. The MASTER-K120S series does not have separated PID module like MASTER-K300S and MASTER-
K1000S series, and the PID function is integrated into the main unit.
The PID control means a control action in order to keep the object at a set value (SV). It compares the SV with a sensor
measured value (PV : Present Value) and when a difference between them (E : the deviation) is detected, the controller
output the manipulate value (MV) to the actuator to eliminate the difference. The PID control consists of three control
actions that are proportional (P), integral (I), and derivative (D).
Set Value
Present Value
The characteristics of the PID function of MASTER-K120S is as following;
• the PID function is integrated into the CPU module. Therefore, all PID control action can be performed with
instruction (PID8,PID8AT) without any separated PID control module.
• P operation, PI operation, PID operation and On/Off operation can be selected easily.
• PWM(Pulse Width Modulation) output is available.
• The manual output (the user-defined forced output) is available.
• By proper parameter setting, it can keep stable operation regardless of external disturbance.
• The operation scan time (the interval that PID controller gets a sampling data from actuator) is changeable for
optimizing to the system characteristics.
• SV Ramp and Delta MV function are available.
MV
SV
P I D
calculation
PV
7-19
Manual MV
Manipulation
value
Automated MV
A/D
module
D/A
Control
object
converting
module
converting
Sensor

Advertisement