LG MASTER-K 120S Series User Manual page 227

Programmable logic controller
Table of Contents

Advertisement

Chapter 8 Communication Functions
(2) Program
(2) Parameter setting for slave station.
① Set parameters as the following table.
Protocol
Communication Method
and mode
Commu-
Station no.
Baud rate
Data bit
Parity bit
Stop bit
Communication channel
Timeout
Dedicated
nication
RS232C null modem or
Enable
31
19200
8
None
1
-
slave
RS422/485
② Slave station does not need program.
③ Baud rate, parity bit, data bit, stop bit setting must be same with master station.
8-37