7) Digital/Analog conversion characteristics
(1) G7F-DA2I
a) 0~20mA output
20 ㎃
10 ㎃
0 ㎃
0V 0
Digital amount 0 outputs analog amount 0mA, 4000 does 20mA.Digital input 1 equals to 5 ㎂ of analog amount.
b) 4~20mA output
20mA
12mA
4mA
0V 0
Digital amount 0 outputs analog amount 4mA, 4000 does 20mA.Digital input 1 equals to 6.25 ㎂ of analog amount.
2000
4000
Digital input
D/A conversion characteristics(Current output)
2000
4000
Digital nput
D/A conversion characteristics(Current output)
5 ㎂
10.005 ㎃
10.000
2000 2001 2002 2003
6.25 ㎂
12.006
12.000
2000 2001 2002 2003