Sub-Menu Heat Curve 2 - Danfoss DHP-A Installation Instructions Manual

Hide thumbs Also See for DHP-A:
Table of Contents

Advertisement

8.2
Sub-menu HEAT CURVE
Table 10.
Used to change settings for the heat curve.
Menu selection
CURVE
MIN
MAX
CURVE +5
CURVE 0
CURVE -5
HEAT STOP
REDUCTION
TANK TEMP
OVERCHARGE
ROOM FACTOR
POOL
POOL HYSTERESIS
8.3

Sub-menu HEAT CURVE 2

Only appears if shunt group sensor is connected and activated in menu SERVICE -> INSTALLATION -> SYSTEM ->
SHUNT GROUP.
Table 11.
Used to change settings for heat curve 2.
Menu selection
CURVE 2
MIN
MAX
48 – Installation instructions VMBMA1002
Meaning
Calculated supply temperature at 0°C outdoor temperature. Shown
as a graphic curve. The curve will be limited by the set values of MIN
and MAX.
Minimum permitted supply temperature, if the temperature for heat
stop has been reached and the heat pump has stopped.
Maximum calculated setpoint value of the supply temperature.
Local increase or reduction of CURVE at an outdoor temperature of
+5°C. Shown in the graph for CURVE.
Local increase or reduction of CURVE at an outdoor temperature of
0°C. Shown in the graph for CURVE.
Local increase or reduction of CURVE at an outdoor temperature of
-5°C. Shown in the graph for CURVE.
Maximum outdoor temperature when heat production is permitted.
If HEAT STOP applies, the outdoor temperature must drop 3°C below
the setting before HEAT STOP stops.
Only appears if the tariff control function has been activated. Lower-
ing set room temperature. Active at 10 kΩ connection at EVU input.
Displayed if buffer tank is active. Charges the buffer tank to the set
temperature. AUTO setting charges the tank to the supply line set-
point value.
Displayed if the buffer tank is active and TANK TEMP is set to AUTO.
Charges the buffer tank to supply line setpoint value + the value of
OVERCHARGE.
Only displayed if an accessory Room temperature sensor is installed.
Determines how great an impact the room temperature is to have
when calculating the supply temperature. For under floor heating it
is recommended that ROOM FACTOR is set to 1, 2 or 3. For radiator
heating it is recommended that ROOM FACTOR is set to 2, 3 or 4.
Only appears if POOL is selected. The temperature in the pool is con-
trolled by a separate sensor regardless of the heating and hot water
system.
Only appears if POOL is selected. The difference between the desired
charge value (adjustable) and actual value to the pool sensor. Pool
hysteresis does not affect the integral value.
Meaning
Calculated shunt group temperature at 0°C outdoor temperature. Shown as a
graphic curve. The curve will be limited by the set values of MIN and MAX.
Minimum permitted shunt group temperature, if the temperature for heat stop
has not been reached.
Maximum permitted shunt group temperature.
Factory setting
40°C
(for under floor heating 30°C)
(range: 22°C / 56°C)
10°C
(range: 10°C / 50°C)
55°C
(for under floor heating 45°C)
(range: 40°C / 85°C)
0°C
(range: -5°C / 5°C)
0°C
(range: -5°C / 5°C)
0°C
(range: -5°C / 5°C)
17°C
(range: 0°C / 40°C)
2°C
(range: 1°C / 10°C)
AUTO
(range: 30°C / 55°C)
0°C
(range: 0°C / 5°C)
2
(range: 0 / 4)
(0 = no impact,
4 = very large impact)
20°C
(range: 5°C /40°C)
2°C
(range: 1°C / 10°C)
Factory setting
40°C
(range: 22°C / 56°C)
10°C
(range: 10°C / 50°C)
55°C
(range: 15°C / 70°C)