Danfoss DHP-A Installation Instructions Manual page 61

Hide thumbs Also See for DHP-A:
Table of Contents

Advertisement

Menu selection Meaning
FACTORY SET
CANCEL = starting point, no changes made.
RADIATOR = reset factory settings for radiator system
FLOOR = reset factory settings for under floor heating
RESET OPER.
0 = no reset of operating times
TIME
1 = reset of operating times to zero
SENSOR CALI-
Following sensors can be found in the installation:
BRATION
OUTDOOR
SUPPLY LINE
RETURN LINE
HOT WATER
BRINE IN
BRINE OUT
DEFR SENSOR
POOL
SHUNT GROUP
HGW TEMPERATURE
BUFFER TANK
2ND HEAT CIR.
SYSTEM SUPPLY
EXTERNAL FACTOR Affects sensors that are installed inside the
heat pump.
VERSION
Shows the software version which is stored on the display card
respectively the I/O-card.
DISPLAY: V X.X
I/O-CARD: V X.X
LOG TIME
Time interval between collection points of temperature history
in minutes. The history graphs always show the 60 last collec-
tion points, which means that the graphs can display history
from 1 hour up to 60 hours ago.
(The function is not active if there is an active alarm).
BRINE TIME ON
The brine pump starts the set number of seconds before the
compressor. Applies at start of heat pump.
BRINE TIME OFF
The brine pump stops the set number of seconds after the com-
pressor. Applies at stop of heat pump.
Factory setting
-
-
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0, (range: -5°C / 5°C)
0 (5°C for DHP-A, DHP-A Opti, DHP-AL,
DHP-AL Opti)
(range: 0°C / 20°C)
-
1M
(range: 1M / 60M)
30S
(range: 10S / 90S)
30S
(range: 10S / 60S)
Installation instructions VMBMA1002 – 59