5.2.2
System solution 2
In system solution 2, the heat pump can produce both heat and hot water and an external auxiliary heater (oil
boiler, electric boiler, district heating or similar) supports heat production but not hot water production. The
exchange valve for heating/hot water is located ahead of the external auxiliary heater, which allows the produc-
tion of heating and hot water at the same time.
The integrated auxiliary heater can be used for heating and hot water production as well as for antilegionella. The
values of the integrals, A2 and A3 are used to select if the external auxiliary heater is to step in before or after the
integrated electrical auxiliary heater.
The heat pump control computer also controls an additional shunt located after the external addition.
For system solution 2, select in menu SERVICE\AUX. HEATER\EXTERNAL ADDITION:
EXT.AUX.HEATER = ON
REV.V. HOT WATER = INT
5.2.2.1 Example system solution 2
System solution for DHP-H, DHP-H Opti, DHP-H Opti Pro, DHP-C, DHP-A, DHP-A Opti.
Figure 20.
Example system solution 2
26 – Installation instructions VMBMA1002
Symbol explanation
1
Heat pump
10
Supply line
11
Return line
12
Cold water
13
Hot-water
36
Circulation pump
51
Supply line sensor, moved out from heat pump
72
Additional shunt
80
Shut-off valve
83
Non-return valve
85
Venting valve
86
Safety valve expansion heating system
87
Safety valve cold water 9 bar
89
Vacuum valve
91
Strainer
96
Flexible hose
113
Expansion heating system
117
External auxiliary heater
126
Safety valve for temperature and pressure (only
applies to certain models)