6.3.2
Connection 230 V, 1-N
Incoming 230V heat pump
Incoming 230V immersion heater
6.3.3
Connection 230 V, 3-P
See country specific electrical instructions.
6.4

Position and connect outdoor sensors

Position the outdoor sensor on the north or north west side of the house.
For higher buildings, the sensor should be positioned between the second and third storeys. Its location must
not be completely protected from the wind but not in a direct draft. The outdoor sensor should not be placed
on reflective panel walls.
The sensor must be positioned at least 1 m from openings in the walls that emit hot air.
If the sensor cable is connected through a pipe, the pipe must be sealed so that the sensor is not affected by
outgoing air.
The outdoor sensor is connected by a two core cable. A maximum cable length of 50 m applies for a cross section
of 0.75 mm2. For greater lengths a cross section of 1.5 mm2 is used, up to a maximum of 120 m.
Then connect the sensor to the heat pump's control system.
Figure 41.
Connection outdoor sensor
40 – Installation instructions VMBMA1002
Circuit-breaker
2
1
4
3
2
1
4
3
Figure 40.
Connection 230V 1N
Terminal block heat pump
Recommended location
Unsuitable location