Table 6. User Settings

Description
Set Date and Time
Display Contrast
Change Language
Set Nominal Output Voltage
Relay Config
Signal Inputs
Serial Port Config
Modem Config
Start Screen
User Password
Audible Alarms
Battery Charging
Automatic Battery Tests
Full Power Battery Test
Number of Battery Strings
Available Settings
Set Month
Date: mm/dd/yyyy
Time: 24:00
Adjust contrast with up/down arrow buttons
Select Language: <English>
Elegir idioma <Español>
Output:
[120V/208V] [127V/220V]
Relay: [Alarm 1] [X-Slot 1-1/2/3/4] or [X-Slot 2-1/
2/3/4]
Setup: [Battery Low] [On Battery] [On Bypass] [UPS
ok] [custom] [empty]
[empty] [Logic]
Signal Input must be wired to the CAN Bridge
Card.
For more information, refer to "Programmable
Signal Inputs" in the Eaton 9355 UPS (10/15 kVA)
User's Guide.
Port: [X-Slot-1] [X-Slot-2/Serv]
Speed: [19200] [9600] [2400] [1200]
Modem Installation
Set Modem Call Events
Set Modem Init String
Set Modem Call Command
Set Modem Communication Password
Eaton logo
Mimic screen
Enabled/Disabled
If Enabled is selected, the password is USER.
Normal Sound/Disabled
ABM cycling/constant
Enabled/Disabled
Enabled automatically runs the battery test once a
month.
Enabled/Disabled
0 through 22
Eaton 9355 Parallel UPS (10/15 kVA) User's Guide 164201601—Rev E0
Operation
Default Setting
01/01/2003
00:00
Moderate
English
120V/208V
Alarm 1: empty
X-Slots (1 or 2)
#1: UPS ok
#2: On Bypass
#3: Summary Alarm
#4: On Battery
<empty>
19200
<Not Installed>
Event #0
Call modem: no
ATZ0
None
None
Eaton logo
Disabled
Normal Sound
ABM cycling
Enabled
Enabled
2 strings for UPS-32 models
51