Page 2
Some configurations are classified under IEC 62040-2 as “C2 UPS for Unrestricted Sales Distribution.” Eaton, ABM, and X-Slot are registered trademarks and ConnectUPS is a trademark of Eaton or its subsidiaries and affiliates. Greenlee is a registered trademark of Greenlee Textron. Modbus is a registered trademark of Schneider Automation.
Page 3
Special Symbols The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK - Observe the warning associated with the risk of electrical shock symbol. CAUTION: REFER TO OPERATOR'S MANUAL - Refer to your operator's manual for additional information, such as important operating and maintenance instructions.
During brownouts, blackouts, and other power interruptions, batteries provide emergency power to safeguard operation. With the Eaton 9355-F47 Unirom UPS, you can safely eliminate the effects of electrical line disturbances and guard the integrity of your systems and equipment. Figure 1 shows the Eaton 9355-F47 Unirom UPS.
Page 8
® increased power protection and control. Optional stabilizing bracket suitable for seismic applications. The following options for the Eaton 9355-F47 Unirom UPS is available: Remote Monitor Panel (RMP) The optional RMP provides monitoring of the operational status and alarm condition of the UPS from virtually any location within the facility.
Proper disposal of batteries or ultracapacitors is required. Refer to your local codes for disposal requirements. Never dispose of batteries or ultracapacitors in a fire. Batteries or ultracapacitors may explode when exposed to flame. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 10
Une mise au rebut réglementaire des batteries est obligatoire. Consulter les règlements en vigueur dans votre localité. Ne jamais jeter les batteries au feu. L'exposition aux flammes risque de les faire exploser. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 11
Es necesario desechar las baterías de un modo adecuado. Consulte las normas locales para conocer los requisitos pertinentes. Nunca deseche las baterías en el fuego. Las baterías pueden explotar si se las expone a la llama. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Hazards associated with this equipment include: Hazardous energy isolation Electric shock hazards Toxic material hazard Falling object hazard Lifting and tip over hazards The following sections describe each hazard. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Dispose of used batteries or ultracapacitor according to your local codes. Falling Object Hazard Objects placed on top of the UPS could cause injury if they fall. Do not place any object on top of the UPS. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
The UPS batteries require careful handling and the use of personal protective equipment (PPE). Before handling batteries, put on rubber gloves and boots, and remove watches, rings, or other metal objects. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
SAFETY OVERVIEW Safety Labels Figure 3 and Table 2 describe the safety and other labels on the UPS. Figure 3. UPS Label Locations 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 19
Hazard Alert WARNING Hazardous Voltage Enclosed Hazard Alert WARNING Hazardous Voltage Enclosed Hazard Alert CAUTION Battery caution, battery rating, battery model number Hazard Alert WARNING Hazardous Voltage Enclosed 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
NOTE Check the battery recharge date on the packaging label. If the date has expired and the batteries were never recharged, do not use the UPS. Contact your service representative. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
18.62” (473 mm) 22.28” (566 mm) Figure 4. Leveling Feet and Casters Clearances The following clearances are recommended for the Eaton 9355-F47 Unirom UPS: From Front of Cabinet 36” (91.4 cm) working space From Back of Cabinet 6” (15.2 cm) 164201642 Rev C www.eaton.com/powerquality...
NOTE If installation is delayed, protect the unpacked UPS from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 24
6. Remove the two M10 bolts securing the rear stabilizing bracket to the pallet (see Figure 5). M10 Bolt M10 Bolt Figure 5. Removing the Rear Stabilizing Bracket Bolts 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 25
See Figure 6. M10 Bolts M4 Screws Front Shipping Bracket M4 Screws (under CB box) Rear Stabilizing Bracket Figure 6. Removing the Brackets 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 26
Figure 7. Unloading the UPS 10. Slowly roll the UPS toward the rear of the pallet. If needed, adjust the leveling feet so that the UPS will roll. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 27
NOTE If installation is delayed, protect the unpacked UPS from moisture, dust, and other harmful contaminants. Failure to store and protect the UPS properly may void your warranty. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
25. NOTE To accommodate the feature of easy system expandability, it is recommended that initial installation of the Eaton 9355-F47 Unirom UPS contain wiring to support the maximum capacity of the UPS. 3. Notify others working in the immediate area that the UPS is under maintenance control.
Page 30
Input and Output Circuit Breakers Control Wiring Terminal Board Conduit Knockouts Figure 9. UPS Rear View 10. Remove the UPS wiring access cover and retain (see Figure 9). 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 31
For a detailed view of the terminal block, see Figure 10. NOTE Input neutral must be wired for proper operation. Failure to connect an input neutral will void the warranty. NOTE The Eaton 9355-F47 Unirom UPS is a single-feed UPS only. Table 3. Terminal Block Wiring Tightening...
Page 32
6. Inspect the crimped terminal to ensure the wire is fully inserted and flush with the end of the wire barrel, and the crimp is centered on the wire barrel. Do not use crimped terminals that do not meet these standards. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 33
Remote EMO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size Remote TB5-1 12–22 AWG 18 AWG (0.82 mm (4–0.32 mm TB5-2 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 34
For a detailed view of the EMO terminal block located on the UPS terminal block, see Figure 10. 14. Replace the UPS wiring access cover. 15. Continue to “Stabilizing the UPS” on page 31. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
3. Use the holes and slots in the bottom of the bracket to attach the UPS to the flooring if desired. 4. Continue to “Internal Battery Installation” on page 33 or “Ultracapacitor Module Installation” on page 45. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
The likelihood of such shock will be reduced if such grounds are removed during installation and maintenance. ELECTRIC ENERGY HAZARD. Do not attempt to alter any battery wiring or connectors. Attempting to alter wiring can cause injury. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 40
RISQUE DE DÉCHARGE ÉLECTRIQUE. N'essayez pas de modifier le câblage ou les connecteurs de la batterie. Vous risqueriez de provoquer des blessures. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 41
PELIGRO DE ENERGÍA ELÉCTRICA. No intente cambiar el cableado o los conectores de las baterías. Intentar cambiar el cableado puede ocasionar lesiones. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
2. Verify that the input and output battery circuit breakers have appropriate lockout/tagout devices installed. UPS Battery Circuit Breaker Input and Output Circuit Breakers Figure 16. UPS Rear View 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 43
Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet (see Figure 17). Figure 17. Removing the Front Cover 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 44
10 M4 screws on the edges of the panel and the M4 screw in the middle of the panel (see Figure 18). M4 Screws Figure 18. Removing the Battery Cover Panel 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 45
11. Secure the batteries to the tray, using 5 spacers and 3 nylon straps. See Figure 19 and Figure 20 for spacer and strap placement. Spacers (5) Nylon Straps Vinyl Caps (12) Figure 19. Battery Tray without Batteries 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 46
13. Load the battery tray into the top tray location in the UPS. 14. Repeat Steps 7 through 13 for the second battery tray. Load the second battery tray into the bottom tray location in the UPS. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 47
15. Connect the two battery trays together by connecting the black connector from the top tray to the red connector from the bottom tray. See Figure 21. Figure 21. Connecting the Battery Trays 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 48
Connect the black connector from the electronics module to the black connector from the bottom tray. Figure 22. Connecting the Battery Circuit Breaker Wires 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 49
“Communication” on page 55 to install UPS communication options, such as X-Slot cards. “Operation” on page 73 to start up the UPS. Remove the lockout/tagout devices before starting up the UPS. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
The module is internally fused to provide additional protection. Attach Black Connector from Electronics Module Attach Red Connector to Red Connector on Electronics Module Figure 23. Ultracapacitor Module 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
ELECTRIC ENERGY HAZARD. Do not attempt to alter any ultracapacitor module wiring or connectors. Attempting to alter wiring can cause injury. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 53
échappe est nuisible à la peau et aux yeux et peut s'avérer extrêmement toxique. DANGER ELECTRIQUE. N'essayez pas de modifier tout connecteur ou câblage l'ultracondensateur. Cela peut provoquer des blessures. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 54
PELIGRO DE ENERGÍA ELÉCTRICA. No intente alterar los cables o conectores del condensador de alta capacidad. Intentar alterar los cables puede causar daños. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
2. Verify that the input and output battery circuit breakers have appropriate lockout/tagout devices installed. UPS Battery Circuit Breaker Input and Output Circuit Breakers Figure 24. UPS Rear View 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 56
Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet (see Figure 25). Figure 25. Removing the Front Cover 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 57
10 M4 screws around the edges of the panel and the single M4 screw in the middle of the panel (see Figure 26). M4 Screws Figure 26. Removing the Internal Cover Panel 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 58
See Figure 27. Upper Shelf with Bushing Red Connector Black Connector Hold Down Screw Hold Down Screw and Washer and Washer Figure 27. Ultracapacitor Module Installed in Cabinet 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 59
“Communication” on page 55 to install UPS communication options, such as X-Slot cards. “Operation” on page 73 to start up the UPS. Remove the lockout/tagout devices before starting up the UPS. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Signal Input 1 X-Slot Communication Bay #2 Signal Input 2 REPO (normally open) REPO (normally closed) DB-9 Communication Port Relay Output Contacts Figure 28. Communication Options and Control Terminals 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
(see Figure 29). Figure 29. Removing the Front Covers 2. Install the appropriate X-Slot card and/or necessary cable(s) into the top cabinet (see Figure 28 and Figure 30). 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 63
With wire cutters, cut either side of the tab and twist down to remove the tab (see Figure 31). Figure 31. Removing Knockout Tabs 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 64
Figure 32. Reinstalling the Front Covers 7. Continue to “Operation” on page 73 to start up the UPS. Remove the lockout/tagout devices before starting up the UPS. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
COMMUNICATION Communication Options The Eaton 9355-F47 Unirom UPS has serial communication capabilities through the DB-9 communication port or through an X-Slot card in one of the available bays. In addition, the power management software can be installed and used to communicate with the UPS via one of the serial communication connections.
X-Slot Cards X-Slot cards allow the UPS to communicate in a variety of networking environments and with different types of devices. The Eaton 9355-F47 Unirom has two available communication bays for any X-Slot card, including: Relay Interface Card - has isolated dry contact (Form-C) relay outputs for UPS status: Utility failure, Low battery, UPS alarm/OK, or On bypass.
Page 67
Web browser interface; connects to a twisted-pair Ethernet (10/100BaseT) network. It is compatible with Eaton IPM/IPP software, Power Xpert monitoring software, and also provides ModBus TCP connectivity to allow setup of UPS shutdown schedules, as well as UPS test and control. In addition, you can attach an Environmental Monitoring Probe to obtain humidity, temperature, smoke alarm, and security information.
Figure 36 shows the enclosure dimensions and cable exit openings. Cable Exit Opening for 1/2” Conduit or Provided Strain Relief Horn Silence Button Figure 35. Remote Monitor Panel 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 69
Provided Strain Relief (3 places) Mounting Slots (6 places) NOTE Matches mounting holes on a single- or Dimensions are in mm [inches] double-gang electrical box. Figure 36. RMP Dimensions 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 70
J1-3 J1-3 Use Beldon 8690 060 or J1-4 J1-4 equivalent cable J1-5 J1-5 J1-6 J1-6 5. Install the IRC into an open X-Slot communication bay (see page 56). 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 71
NOTE Conduit and wiring supplied by the customer. The maximum distance between the RMP and the UPS is not to exceed 152.4m (500 ft). Figure 37. RMP Top Internal View 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
IRC still does not operate correctly, replace the fuse. If this does not correct the problem, contact your service representative for verification that the IRC is working correctly. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
It also gives you a complete record of critical power events, and it notifies you of important UPS or power information. If there is a power outage and the Eaton 9355-F47 Unirom UPS battery power becomes low, power management software can automatically shut down your computer system to protect your data before the UPS shutdown occurs.
Normally Open Figure 39. External Control Terminal Connections NOTE If using a semiconductor switch type, pay attention to the proper polarity. A relay or other mechanical control is preferred. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
UPS when the emergency power-off function is activated. REPO Connections Wire Function Terminal Wire Size Rating Suggested Wire Size REPO 12–22 AWG 18 AWG (0.82 mm (4–0.32 mm 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
NOTE See Figure 39 on page 68 for the polarity and verify these connections if polarity control is required. The default and programmable settings for the signal inputs are shown in Table 8. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 77
If active, the UPS knows that input is fed from the generator. Bypass is disabled; the automatic battery test is disabled. External Transformer This option is not used. Overtemperature 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 78
COMMUNICATION 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Chapter 10 Operation This chapter contains information on how to use the Eaton 9355-F47 Unirom, including front panel operation, and UPS startup and shutdown. Control Panel Functions The UPS has a four-button graphical LCD with backlight. It provides useful information about the UPS itself, load status, events, measurements, and settings (see Figure 40).
Display Functions As the default or after 15 minutes of inactivity, the LCD displays the selectable startup screen. The default is the Eaton logo and can be changed to the Mimic screen in the User Settings menu. The backlit LCD automatically dims after a long period of inactivity. Press any button to restore the screen.
Page 81
UPS Type / Part Number / Serial Number / Firmware / Display / CAN Bridge NOTE The CAN Bridge option is not used. Turn UPS ON/OFF ON and OFF Options 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Set Modem Communication Password None Start Screen Eaton logo Eaton logo Mimic screen User Password Enabled/Disabled Disabled If Enabled is selected, the password is USER. Audible Alarms Normal Sound/Disabled Normal Sound 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 83
Control Commands from X-Slot2/Serv Allowed/Disabled Allowed X-Slot Signal Input Activation Delay 0 through 65 seconds Input signal delayed shutdown delay 1 through 65535 seconds 120s Site Wiring Fault Notice Enabled/Disabled Enabled 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Initial Startup Startup and operational checks must be performed by an authorized Eaton Customer Service Engineer, or the warranty terms as specified on page W-105 become void. This service is offered as part of the sales contract for the UPS. Contact service in advance (usually a two-week notice is required) to reserve a preferred startup date.
The UPS stops supplying power to the load. 5. Switch the UPS battery circuit breaker to the OFF position. The UPS disconnects from the batteries and is on logic power only. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
1. Press the large red EMO switch on top of the UPS. The UPS immediately stops supplying power to the load. The UPS disconnects from the batteries and opens the input and output breakers. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Verify that the battery circuit breaker is in the OFF position. Avoid temperature and humidity extremes. To maximize battery life, the recommended storage temperature is 59°F (15°C) to 77°F (25°C). 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Replace/change the batteries approximately every five years. Battery Type The following battery type is supplied with the UPS. Only the following type is recommended. Use of any other battery type inside Eaton cabinets will void the product warranty. C A U T I O N When replacing batteries, use the same manufacturer and part number originally supplied with the UPS to ensure correct harness fit and terminal landing.
4. Verify the absence of hazardous energy according to Table 1 on page 9. UPS Battery Circuit Breaker Input and Output Circuit Breakers Figure 41. UPS Rear View 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 92
Press and release the handle latch at the bottom of the cover and then lift the cover up and off the cabinet (see Figure 42). Figure 42. Removing the Front Cover 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 93
10 M4 screws on the edges of the panel and the M4 screw in the middle of the panel (see Figure 43). M4 Screws Figure 43. Removing the Battery Cover Panel 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 94
Disconnect the black connector from the electronics module from the black connector from the bottom tray. Figure 44. Disconnecting the Battery Circuit Breaker Wires 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 95
Adjust the table so its height is level with the top battery tray. 10. Place the spike of a T-bar handle through one of the holes on the top battery tray lip. Pull the tray onto the table. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 96
17. Secure the batteries to the tray, using 5 spacers and 3 nylon straps. See Figure 46 and Figure 47 for spacer and strap placement. Spacers (5) Nylon Straps Vinyl Caps (12) Figure 46. Battery Tray without Batteries 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 97
18. Load the battery tray into the top tray location in the UPS. 19. Repeat Steps 9 through 18 for the second battery tray. Remove and load the second battery tray at the bottom tray location in the UPS. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 98
20. Connect the two battery trays together by connecting the black connector from the top tray to the red connector from the bottom tray. See Figure 48. Figure 48. Connecting the Battery Trays 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 99
Connect the black connector from the electronics module to the black connector from the bottom tray. Figure 49. Connecting the Battery Circuit Breaker Wires 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
C A U T I O N Do not discard waste electrical or electronic equipment (WEEE) in the trash. For proper disposal, contact your local recycling/reuse or hazardous waste center. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
UPS with one battery section or ultracapacitor module 10 kVA, 9 kW 15 kVA, 13.5 kW Table 12. Dimensions and Weights Dimensions (H Weight 36.7” 12” 33.5” (93 85 cm) 410 lb (186 kg) 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 102
<62 dBA for heavy load, high ambient or high altitude, on battery Surge Suppression ANSI C62.41 Category B3 Safety Conformance NOM-019-SCFI, UL 1778, CSA C22.2, No. 107.3; Agency Markings cULus EMC (Class A) IEC 62040-2, FCC Part 15, ICES-003 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 103
50/60-Hz selectable or auto‐configuring Output Frequency Regulation Synchronization to line Output Overload 101–110% for 10 minutes 111–125% for 60 seconds 126–149% for 5 seconds >150% for 300 milliseconds 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 104
Allows start of UPS without utility input Performance ABM technology increases battery service life, optimizes recharge time, and provides a warning before the end of useful battery life 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Page 105
Verify that the MSDS you read is issued by the manufacturer and not by a third party. Vital information may differ between MSDS versions issued for the same material. The manufacturer is responsible for specifying all safety information. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Chapter 13 Troubleshooting The Eaton 9355-F47 Unirom UPS is designed for durable, automatic operation and also alerts you whenever potential operating problems may occur. Usually the alarms shown by the control panel do not mean that the output power is affected. Instead, they are preventive alarms intended to alert the user.
Press any button on the front panel display to silence the alarm. If the alarm status changes, the alarm beeps again, overriding the previous alarm silencing. 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
Please have the following information ready when you call for service: Model number Serial number Firmware version number Date of failure or problem Symptoms of failure or problem Customer return address and contact information 164201642 Rev C www.eaton.com/powerquality Eaton 9355-F47 Unirom UPS (10/15 kVA) User's Guide...
For Product installed (and currently located) in the fifty (50) United States and the District of Columbia, if, in the opinion of Eaton, a Warranted Item is defective, Eaton's sole obligation, at the option of Eaton, will be to refurbish or replace such defective Warranted Item (including the costs of providing diagnosis, service, and labor [“labor...
Page 112
(including interest charges, if any). During such time as Eaton has not received payment of any amount due to it for the Product, in accordance with the contract terms under which the Product is sold, Eaton shall have no obligation under this Warranty.