SETUP AND ADJUSTMENT

The EE210 transmitter is ready to use and does not require any confi guration by the user. The factory setup of EE210 corresponds to the
type number ordered. (Ordering guide please see data sheet at www.epluse.com/EE210.)
If needed, the user can change the factory setup by using the optional E+E Product Configuration Adapter (EE-PCA) and the E+E
Product Configuration Software (EE-PCS).
PC
One can assign other physical quantities to the analogue outputs, change the scaling of the outputs and perform one or two point ad-
justment for humidity and temperature.
For confi guration with EE-PCA and EE-PCS both 4-20 mA two-wire outputs must be connected.
For product data sheets EE-PCS and EE-PCA please see www.epluse.com.
The E+E Product Configuration Software (EE-PCS) is free and can be downloaded from www.epluse.com/configurator.

MAINTENANCE

When employed in dusty, polluted environment:
The filter cap shall be replaced once in a while with an E+E original one. A polluted filter cap causes longer response time of the
device.
If needed, the sensing head can be cleaned. For this remove first very carefully the filter cap. Take care not to hit the sensing
head. Shake slowly the sensing head for one minute in a solution of 50% isopropyl alcohol with 50% distilled water. Then the sen-
sing head shall be rinsed with cold tap water and let dry freely. Do not touch or rub the sensing head! After cleaning the sensors
install carefully a new E+E original filter cap.
ACCESSORIES
Configuration kit: The confi guration kit allows user setup for the output scaling and for the interface parameters, as well as humidity
and temperature adjustment of the sensor.
Position 1:
- configuration adapter (incl. USB cable for PC)
Position 2:
- cable for configuration adapter
Position 3:
- configuration software:
free of charge; download:
www.epluse.com/EE210
Position 4 - optional:
- power supply for EE210
USA
FCC notice:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio
frequency energy and, if not installed and used in accordance with the installation manual, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
- Reorient or relocate the receiving antenna.
- Increase the separation between the equipment and receiver.
- Connect the equipment into an outlet on a circuit different from that to which thereceiver is connected.
- Consult the dealer or an experienced radio/TV technician for help.
CANADIAN
ICES-003 Issue 5:
CAN ICES-3 B / NMB-3 B
INFORMATIONEN
Langwiesen 7 • A-4209 Engerwitzdorf
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
info@epluse.com • www.epluse.com
LG Linz Fn 165761 t • UID-Nr. ATU44043101
Place of Jurisdiction: A-4020 Linz • DVR0962759
HA011062
HA011050
EE-PCA
HA011062
EE-PCS
V03
+43 7235 605 0 / info@epluse.com
V03
(optional)
BA_EE210_e // v1.3 // Modification rights reserved

Advertisement

loading