sEtuP ANd AdJustmENt

The EE820 transmitter is ready to use and does not require any configuration by the user. The factory setup of EE820 corresponds to
the type number ordered. For ordering guide please see data sheet at
If needed, the user can change the factory setup by using the optional Product Configuration Adapter EE-PCA and the Product
Configuration Software EE-PCS. One can change the output signal, the scaling of the output and perform CO
PC
Changing the output signal:
The output signal can be changed from voltage to current or vice-versa.
Set the output signal selection switch to I for current 4 - 20 mA output or to U for voltage 0 - 10 V output. The original CO
does not change and the calibration data remains valid.
Example:
Factory setup: voltage output (U), output scale: 0 - 10 V = 0 - 5000 ppm
User setup (after setting the output signal selection switch to I): current output (I), output scale: 4 - 20 mA = 0 - 5000 ppm.
Changing the output scale:
The scaling of the output can be changed by using EE-PCA and EE-PCS.
Example:
The initial scaling of the output is 4 - 20 mA = 0 - 5000 ppm.
Important:
After changing the factory setup (output signal and/or output scale) the original type number on the EE820 identification label loses
its validity; it does not match any longer the device setup.
The return to factory setup function of EE-PCS restores the original adjustment/calibration of the device, but does not affect the user
setup for output signal and output scale.
For EE-PCA product data sheet please see
The EE-PCS Product Configuration Software is available for free download at

mAiNtENANCE

Even in case of use in dirty and dusty environment, the electronics of EE820 are very well protected by the enclosure and the filter on
the front cover. Do not attempt in any way to clean the inside of the device.
In case of dirt deposits on the exterior of the device, this can be cleaned by weeping it gently with a soft, light wet cloth. The enclosure
must be closed during the cleaning. Do not use solvent-based cleaning agents; these might affect the enclosure and the labels. Do not
attempt to clean the filter on the front cover, as it would only lead to its faster clogging.
In a polluted environment, the filter on the front cover of EE820 might get clogged in a long run. This is more likely to happen for the
EE820 with forced air circulation. Longer response time indicates a clogged filter. In such a case the entire front cover shall be replaced
by an original new one.
HA011062
EE-PCA
The output scale after the change can be 4 - 20 mA = 400 - 4000 ppm.
www.epluse.com/EE820
www.epluse.com/EE820
EE820
www.epluse.com/configurator.