Basic Setup; Default Values For Commissioning; Meter Setup - Siemens 9410 Series User Manual

Hide thumbs Also See for 9410 Series:
Table of Contents

Advertisement

9410 series

Basic setup

Default values for commissioning

Meter setup

Volts mode
PT/CT setup
18
Use these default settings for the first time you connect to and configure your meter.
Parameter
Display password (also for logging onto meter webpages)
Username (for logging onto meter webpages)
IP address
Subnet mask
Gateway
Unit ID
Language
You can configure your meter's basic metering parameters using the display.
Parameter
Values
Volts Mode
4W-Wye, Delta, 3W-Wye,
Single, Demo
PhaseOrder
ABC, ACB
Parameter
Values
PT Primary
1 to 999,999.99
PT Secondary
1 to 999,999.99
CT Primary
1 to 999,999.99
CT Secondary
1 to 999,999.99
I4 Primary
1 to 999,999.99
I4 Secondary
1 to 999,999.99
Default value
0
9410
169.254.0.10
255.255.0.0
0.0.0.0
1
English
Description
The power system's configuration
The power system's phase order
Description
The potential transformer's primary winding voltage
rating
NOTE: PTs are also referred to as a VTs or
voltage transformers.
The potential transformer's secondary winding
voltage rating
NOTE: PTs are also referred to as a VTs or
voltage transformers.
The current transformer's primary winding current
rating
The current transformer's secondary winding
current rating
The I4 current transformer's primary winding
current rating
The I4 current transformer's secondary winding
current rating
Basic setup
7EN05-0336-03