Installation - Fuji Electric FRENIC-HVAC Series Instruction Manual

Combination vfd, ul/nema type 1 & type 12
Hide thumbs Also See for FRENIC-HVAC Series:
Table of Contents

Advertisement

Installation

CAUTION
The FRENIC-HVAC Combination VFD should be located:
Away from flammable or combustible liquids, gases, and other materials
Away from sources of severe dust, metal shavings, or other particulate
material
Away from corrosive liquids, spray, or mist
Away from sources of heat
Where the ambient temperature will remain between -10°C (14°F) and 40°C
(104°F)
Where the elevation is 3300ft or lower, above this level requires derating the
current
Wall-mount panels must be mounted to a surface that is capable of supporting the
weight of the panel.
Refer to the Outline/Layout drawing that shipped with the panel for required clearances.
Routing of field wiring should be planned in coordination with choosing a mounting
location.
Disconnect – Motor branch circuit protection to be provided by customer/others per table
on next page.